Pneumatic butterfly valve common failures and solution

Pneumatic butterfly valve common failures and solutions


Fault phenomenon  

Check Item

Solution

Pneumatic butterfly valve can’t open

1,   Whether the reversing solenoid valve plug, stuck, causing air can’t enter or out of the cylinder.

1Use air pipe directly to the pneumatic actuator two holes, if normally work, then the solenoid valve has a problem, need to change a solenoid valve.

2Air supply pressure less than 5KG.

2To increase the gas source to 5KG or increased to 6KG.  

3Pneumatic actuator leakage air, cannot normally working.

3Replace a new actuator.

Pneumatic butterfly valve can’t closed tightly / Leakage

1Whether the solenoid valve plug, stuck, causing the air cannot enter or out of the cylinder.   

1Use air pipe directly to the pneumatic actuator two holes, if normally work, then the solenoid valve has a problem, need to change a solenoid valve.

2Air supply pressure less than 5KG.

2To increase the gas source to 5KG or increased to 6KG.

3Pneumatic actuator leakage air, cannot normally working.

3Replace a new actuator.

4The pneumatic actuator of the position limit stop is loose, causing the pneumatic actuator is in the place, the butterfly valve is not in place.

4Reset the pneumatic actuator “close” position stop. Make the butterfly valve keep in with the pneumatic actuator.

Pneumatic butterfly valve closed too tightly / Leakage

4The pneumatic actuator of the position limit stop is loose, causing the pneumatic actuator is in the place, the butterfly valve is closed over or too tightly.

4Reset the pneumatic actuator “close” position stop. Make the butterfly valve keep in with the pneumatic actuator.

 

 


 